Humidification - Calculation

Humidification - Calculation

Program that allows you to quickly calculate the quantity of steam needed in kg/h to humidify a room. It also provides the values ​​of the power needed in kW for vaporization.

We are pleased to present you an innovative program that will take you through the complex world of calculating the amount of steam needed to humidify a room. In an era where people's well-being and health are increasingly linked to the quality of the air we breathe, accurately understanding and managing humidity has become crucial.

This program was created by Itieffe to simplify the calculation process, making it accessible to everyone, from HVAC professionals to simple enthusiasts. It will guide you step by step in determining the amount of steam needed to achieve the desired level of humidity in a specific environment.

We hope this program becomes your reliable guide to tackling your humidification challenges. Whether you are a technician, a designer or simply interested in improving the quality of the air that surrounds us, we are here to help you calculate the amount of steam needed to create healthier and more comfortable environments.

Let's start this journey together, discovering how to calculate the amount of steam needed to humidify and its crucial impact on our quality of life.

Humidification - Calculation

Process that allows you to quickly calculate the amount of steam required in kg / h to humidify an environment.

It also provides the values ​​of the power required in kW for vaporization.

Instructions

The program is very easy to use.

However, the indications for its use are reported below.

Data entry

1 - enter the values ​​of the external temperature and its relative humidity (0 ° C - 80% RH);

2 - enter the values ​​of the environmental conditions of temperature and relative humidity (20 ° C - 55% Ur);

3 - enter the quantity of external air that will have to undergo the humidification treatment (3.000 m3/ H).

Let's go read the results

4 - the quantity of steam required in the environment is equal to: 17,9 kg / h;

5 - the power required to produce the required steam is equal to: 12,5 kW.

Remember that the air to be humidified is only that coming from the renewal.